VCBA S2 VERSION 4.xx SOFTWARE MANUAL REV 3
77
6. From the “Timing Window” radio box group, select “1 second”. The 1 second timing
window should always be used since it provides the required adequate resolution (±50
micro-seconds) for dynamic tests.
7. From the “Insertion Resistor” radio box group, select the desired insertion resistance
value.
8. Check the “Dynamic Resistance” checkbox.
9. From the “Trigger Type” radio box group, select the trigger type.
10. Click on the “OK” button. The following window will be displayed:
11. A 5-second timer will count down, and then the test will be initiated. A sequence of
status messages will be displayed. When the test is complete, the data will be
transferred from the CB analyzer to the PC. When the data has been transferred to the
PC, the results will be displayed in the VCBA S2 software. The test record will also be
saved in the location selected in step 4.