VCBA S2 VERSION 4.xx SOFTWARE MANUAL REV 3
59
Open and Close analysis points can also be defined in this section.
NOTES
Contact Point #1 is the distance from the fully closed position to the position
when contact #1 opens.
Percentage of Stroke is the distance from the fully closed position to the
second analysis point represented as percentage of the total stroke distance.
Distance from Close is the user-defined distance from the fully closed position
to the first analysis point.
Contact #1 + Time is the time to add to Contact #1’s Open position time. This
new position defines an analysis point to calculate velocity.
Contact #1 – Time is the time to subtract from Contact #1’s Open position
time. This new position defines an analysis point to calculate velocity.
The VCBA S2 software supports both Metric and English units. The units of measure can be set
from the “Measure Unit” dropdown list in this section.
The “Manual Override” option can be used to select a velocity calculation formula.